Ring Main Unit (RMU) Technical Data Sheet

*Used in power distribution ring networks, compact in size. Insulation types include gas-insulated (SF6) and solid-insulated/air-insulated.*

WhatsApp:

Share to

  • 产品描述
  • Used in power distribution ring networks, compact in size. Insulation types include gas-insulated (SF6) and solid-insulated/air-insulated.

     

    Parameter

    Unit

    Standard Parameter Value

    Detailed Description / Special Requirements

    Rated voltage

    kV

    12

     

    Rated current

    A

    630

    For load switchgear

    Rated short-time withstand current

    kA/s

    20/3, 20/4, 31.5/3

    31.5kA is commonly used for fuse combination units

    Rated lightning impulse withstand voltage

    kV

    75

    Phase-to-earth; 85kV required across the isolating gap

    Degree of protection

    -

    IP4X

    Enclose

    Arc duration

    s

    0.5

    Internal arc fault test

    Annual gas leakage rate

    %/y

    ≤ 0.1

    Applicable only to SF6 gas-insulated units

    Service life

    year

    ≥ 40

     